Features
■ Using hight sensitive heat-sensing componentsto effectively detect fires with good stability.
■ A light guide makes the alarm visible fromall angles.
■ Activation: Red light
Fault: Green light
Standby: Green light flashing
■ Optional function : reed switch test function
Specifications
■ Rated voltage : DC 24V
■ Rated current : 25mA
■ Current monitor : 35μA
■ Relative humidity : 0~95%
■ Ambient temperature : 0oC~+50oC
■ Dimensions : ø102.6mm x 49.5(H)mm
■ Weight : 103g
Activating Time |
30°C higher than room temperature, and activate within 30 seconds at 85cm/s wind speed; or the average temperature rises 15°C per minute at room temperature, activate within 4.5 minutes |